To ensure the reliability, safety, and energy efficiency of our shared infrastructure, all customers must strictly follow these cabinet installation rules. Non-compliance directly impacts your Service Level Agreement (SLA), voids applicable service credits, and may trigger mandatory intervention.
Airflow & Cooling

- Front-to-Back Flow: Equipment must be installed matching the conditioned air direction. The air inlet must face the cold aisle, and the exhaust must face the hot aisle.
- Inverted Airflow Prohibited: Deploying devices causing reverse/inverted airflow is strictly forbidden. It risks equipment damage and wastes critical energy. Some network equipment uses reversible fans. Ensure the correct fan direction is set before installation. In other cases, change the switch orientation.
- Blanking Panels: All unused rack units must be completely sealed with blanking panels to prevent hot exhaust recirculation. Panels are available in cabinets in the hallways or your rack room.
- Enforcement: If reverse airflow or open gaps are detected, Leaseweb will notify you. If unresolved, Leaseweb reserves the right to access your rack to correct the configuration directly, as per Clause 12.9 (vi) of the Services Specifications and Clause 34.3 (ii) of our Policies. This may cause downtime and/or incur extra costs. Periodic audits will be performed.
Racking & Mechanical Setup
- Data Center Equipment: Use only professional hardware designed for datacenter use. Consumer-grade power strips, electronics, or modified power equipment are not permitted.
- Weight Distribution: Position heavy hardware (e.g., dense storage arrays) at the bottom of the rack. Build from the bottom up to prevent top-heavy cabinets and ease installation.
- Secure Mounting: Stacking unmounted or loose equipment is prohibited. All devices must be securely installed using cage nuts and/or dedicated rails. Equipment must fit within one (1) or multiple U’s.
- Door Clearance: Hardware, structural rails, and wiring looms must not protrude or obstruct the front or rear cabinet doors from closing smoothly.
Power & A+B Feed Redundancy
- Dual-corded Systems: Equipment with redundant power supplies (PSUs) must connect to different PDUs for true redundancy.
- Single-corded Systems: For devices with a single PSU, use an ATS/STS or ensure the service itself is redundant.
- Phase Balancing & Capacity: Maintain balanced loads between both PDUs. Never exceed your contracted power commitment. The remaining active feed must handle 100% of the total rack load if one circuit drops. For 3-phase racks, do not mix phases.
Network & Structured Cabling
- Demarcation & Inter-Cabinet Wiring: Leaseweb is exclusively responsible for providing and routing all infrastructure cross-connects and uplinks between racks.
- Cable Type: Leaseweb standardizes on SMF fiber for cross-connects with LC connectors. LR or LX/LH optics can be used.
- Cable Management: Use vertical and horizontal managers to route cables safely. Do not allow slack cables or unmanaged bundles to block server fan exhausts.
Cleanliness & On-Site Rules
- Unpacking Rules: Unpacking inside server rooms is strictly prohibited. Use the designated staging room.
- Housekeeping: Leave the cabinet surroundings broom clean. Food, drinks, or other liquids are totally banned on the data center floor.
Protection
- Please use ear protection inside the data halls.